10.16 - Final Quick Reference

Module: Universal Review and Mock Examinations
Purpose: Final compact review for EPA Section 608 Universal certification preparation
Covers: Core, Type I, Type II, and Type III high-priority facts from Modules 1–10
Current regulatory verification basis: August 14, 2026
Use: Final rapid review only. If a rule or condition is unclear, return to the detailed course section rather than memorizing an isolated number.


1. Universal Master Table

ItemCoreType IType IIType III
Primary scopeCommon environmental, regulatory, recovery, safety, and refrigerant knowledgeSmall appliancesMedium-, high-, and very-high-pressure appliancesLow-pressure appliances
Typical equipmentApplies across all typesRefrigerator, window A/C, dehumidifier, qualifying packaged terminal unitSplit system, heat pump, rooftop unit, walk-in, supermarket rackLow-pressure centrifugal or absorption chiller
Classification keyCommon knowledgeFactory manufactured + factory charged + factory hermetically sealed + 5 lb or lessRefrigerant pressure category; not Type I or Type IIIRefrigerant saturation pressure below 45 psia at 104°F
Recovery emphasisRecover, recycle, reclaim; equipment and cylinder fundamentals80% / 90% recovery or 4 in. Hg vacuum alternativeBulk liquid first where practical, vapor finish, pressure-rebound checkLiquid first, vapor second, water/freezing control
Evacuation / removal requirementKnow pressure/vacuum units and current Table 1 logicPercentage requirement or 4 in. Hg vacuum alternativeCurrent Table 1: 0 / 4 / 10 / 15 in. Hg vacuum, depending on conditions25 mm Hg absolute
Major-repair relevanceKnow definition and service-practice rulesType I recovery/service procedures controlMajor-repair definition and Table 1 are high priorityMajor-repair and low-pressure service provisions apply
Leak-repair emphasisKnow applicability and current-vs-historical distinctionNot defined by Type I classificationCurrent Section 608 ODS leak-repair rules are frequently testedSame federal applicability logic; Type III classification alone does not create leak-repair applicability
Charging emphasisCorrect refrigerant, avoid contamination, blend handlingFollow appliance/refrigerant procedureFollow manufacturer procedure; blend composition mattersFrom deep vacuum: vapor first, liquid later
Primary safety emphasisPPE, ventilation, cylinders, nitrogen, fire/electrical hazardsFrostbite, cylinder/access safetyHigh pressure, compressor/discharge safety, relief protectionFreeze risk, pressure relief, machinery-room and water-side hazards
Common trapCorrect fact used in wrong context≤5 lb alone is not enough15 lb, 50 lb, and 200 lb are different rules25 mm Hg absolute is not 25 in. Hg vacuum

Universal Certification Relationship

CORE
+
TYPE I
+
TYPE II
+
TYPE III
→ UNIVERSAL

Core is the common examination section. It is not a fourth appliance type.


2. Classification First

Before selecting a recovery rule, evacuation value, or service procedure:

1. IDENTIFY THE APPLIANCE
2. CHECK MVAC / MVAC-LIKE STATUS
3. CHECK THE COMPLETE SMALL-APPLIANCE DEFINITION
4. IF NOT TYPE I, DETERMINE PRESSURE CATEGORY
5. IDENTIFY THE SERVICE CONDITION
6. THEN SELECT THE RULE

Fast Classification

Factory manufactured
+
factory charged
+
factory hermetically sealed
+
≤5 lb refrigerant
→ TYPE I
Medium / high / very-high pressure
→ TYPE II
Low pressure
→ TYPE III
Type I + Type II + Type III
→ UNIVERSAL

3. Core Final Summary

Environmental and Regulatory

Clean Air Act Section 608
→ U.S. stationary refrigerant-management program
Montreal Protocol
→ international ozone-depleting-substance control framework
Stratospheric ozone
→ protects against harmful UV
CFC / HCFC
→ contain chlorine
→ nonzero ODP
HFC / HFO
→ no chlorine
→ zero ODP

Zero ODP does not mean zero GWP, zero flammability, zero toxicity, or permission to vent.

Venting

DO NOT knowingly vent covered refrigerant
during maintenance, service, repair, or disposal

Limited permitted releases include properly defined de minimis releases associated with good-faith recovery and specific exempt substitutes/end uses.

Nitrogen alone
→ may be released after proper testing
Nitrogen + covered refrigerant
→ do not intentionally vent the mixture

Recover, Recycle, Reclaim

RECOVER
→ REMOVE + STORE
RECYCLE
→ CLEAN FOR PERMITTED REUSE
RECLAIM
→ REPROCESS + VERIFY PURITY

Recovery Equipment

SYSTEM-DEPENDENT
→ depends on appliance components and/or refrigerant pressure
SELF-CONTAINED
→ has its own independent recovery means
FULL CHARGE >15 lb
→ ordinary system-dependent equipment prohibited
→ unless permanently attached as a pump-out unit

Recovery Cylinders

RECOVERY CYLINDER
→ refillable
DISPOSABLE CYLINDER
→ do not refill
→ do not use for recovery

Use a scale and do not overfill.

Project exam-preparation concept:

80% maximum fill concept

Any lower manufacturer, transportation, or refrigerant-specific limit controls actual field use.

Pressure and Vacuum

psig
→ referenced to atmosphere
psia
→ referenced to perfect vacuum
0 psig
≠
0 psia
in. Hg vacuum
→ larger number = deeper vacuum
mm Hg absolute / microns
→ smaller number = deeper vacuum

Nitrogen Safety

Use:

DRY NITROGEN
+
PRESSURE REGULATOR
+
DOWNSTREAM RELIEF PROTECTION

Never use oxygen or compressed air for refrigerant-system pressure testing.

Section 608 Versus Section 609

SECTION 608
→ stationary appliances
SECTION 609
→ MVAC service for consideration

Universal Section 608 certification does not replace Section 609 certification for paid MVAC service.

Vehicle-mounted cargo refrigeration is not automatically an MVAC.


4. Type I Final Summary

Small-Appliance Definition

All four conditions are required:

FACTORY MANUFACTURED
+
FACTORY CHARGED
+
FACTORY HERMETICALLY SEALED
+
5 lb OR LESS
≤5 lb ALONE
≠
TYPE I

Type I Recovery Requirements

ConditionRequirement
Recovery/recycling equipment manufactured before Nov. 15, 199380% recovery
On/after Nov. 15, 1993 + appliance compressor functional90% recovery
On/after Nov. 15, 1993 + appliance compressor nonfunctional80% recovery
Alternative4 in. Hg vacuum

Remember:

THE DATE APPLIES TO THE RECOVERY EQUIPMENT
NOT THE APPLIANCE
THE COMPRESSOR CONDITION REFERS TO
THE APPLIANCE COMPRESSOR

Operating Compressor

OPERATING COMPRESSOR
→ compressor assists refrigerant movement
→ high-side recovery emphasis

Failed Compressor

FAILED COMPRESSOR
→ no compressor pumping assistance
→ high + low access as needed

Controlled heat may help release trapped refrigerant.

Never use an open flame.

Access Fittings

PROCESS STUB
→ tubing
PIERCING / SOLDERLESS ACCESS FITTING
→ temporary service access

Current Type I exam emphasis:

REMOVE TEMPORARY SOLDERLESS FITTING
AFTER SERVICE
→ restore / reseal tubing
→ leak check

Disposal

Final processor:

RECOVER REMAINING REFRIGERANT
OR
VERIFY ACCEPTABLE PRIOR RECOVERY

Prior-recovery signed statement:

NAME
+
ADDRESS
+
DATE

Required final-processor statements/contracts:

KEEP 3 YEARS

A sticker alone is not sufficient prior-recovery verification.


5. Type II Final Summary

Type II Scope

MEDIUM
+
HIGH
+
VERY HIGH PRESSURE
→ TYPE II

Pressure Categories

CategoryCurrent Classification
Low<45 psia at 104°F
Medium45–170 psia at 104°F
High170–355 psia at 104°F
Very highCritical temperature below 104°F, or liquid-phase saturation pressure >355 psia at 104°F

High-pressure appliance classification is not the same as the high side of a refrigeration system.

Recovery Sequence

PREPARE SYSTEM + CYLINDER
→ RECOVER ACCESSIBLE BULK LIQUID FIRST
→ RECOVER REMAINING VAPOR
→ REACH REQUIRED ENDPOINT
→ ISOLATE
→ CHECK PRESSURE REBOUND

Pressure rebound can come from:

  • Refrigerant evaporating from cold components.
  • Refrigerant leaving compressor oil.
  • Refrigerant trapped in isolated sections.
FIRST LOW PRESSURE READING
≠
AUTOMATICALLY COMPLETE

System-Dependent Restriction

FULL CHARGE >15 lb
→ no ordinary system-dependent recovery equipment
→ unless permanently attached pump-out unit

The rule uses full charge, not the amount remaining after a leak.

Type II Evacuation Table

Recovery Equipment Manufactured On or After November 15, 1993

ApplianceRequired Level
Very-high pressure0 in. Hg vacuum
High pressure, <200 lb full charge0 in. Hg vacuum
High pressure, ≥200 lb full charge10 in. Hg vacuum
Medium pressure, <200 lb full charge10 in. Hg vacuum
Medium pressure, ≥200 lb full charge15 in. Hg vacuum

Recovery Equipment Manufactured Before November 15, 1993

ApplianceRequired Level
Very-high pressure0 in. Hg vacuum
High pressure, <200 lb full charge0 in. Hg vacuum
High pressure, ≥200 lb full charge4 in. Hg vacuum
Medium pressure, <200 lb full charge4 in. Hg vacuum
Medium pressure, ≥200 lb full charge4 in. Hg vacuum

Major Maintenance, Service, or Repair

Major if removing:

  • Compressor.
  • Condenser.
  • Evaporator.
  • Auxiliary heat-exchange coil.

Also major if:

OPENING >4 in² OF FLOW AREA
+
OPEN >15 MINUTES
FILTER-DRIER REPLACEMENT
≠
AUTOMATICALLY MAJOR

Special Service-Pressure Concepts

When all regulatory conditions are satisfied:

QUALIFYING NON-MAJOR OPENING
→ NO HIGHER THAN 0 psig
LEAK PREVENTS NORMAL TABLE 1 ENDPOINT
→ isolate where possible
→ non-leaking portion to Table 1
→ leaking portion to lowest attainable
→ not above 0 psig
SPECIAL OIL-CHANGE PROVISION
→ NO HIGHER THAN 5 psig

Current Section 608 ODS Leak-Repair Triggers

For qualifying appliances containing 50 lb or more of applicable ozone-depleting refrigerant:

End UseCurrent Trigger
Industrial process refrigeration30%
Commercial refrigeration20%
Comfort cooling10%
Other qualifying appliances10%
35% / 15%
→ HISTORICAL
→ NOT THE CURRENT SECTION 608 TABLE

Do not confuse the Section 608 ODS framework with the separate current AIM Act HFC leak-repair framework.

Type II Safety

RECIPROCATING COMPRESSOR
+ CLOSED DISCHARGE SERVICE VALVE
→ DO NOT ENERGIZE
HERMETIC COMPRESSOR
+ DEEP VACUUM
→ DO NOT ENERGIZE
HIGH HEAD PRESSURE
→ diagnose cause
→ do not bypass safety control

Verify pressure ratings for recovery machines, hoses, gauges, cylinders, and fittings on very-high-pressure systems.


6. Type III Final Summary

Low-Pressure Classification

<45 psia at 104°F
→ LOW PRESSURE
→ TYPE III

Many low-pressure chillers operate below atmospheric pressure.

Therefore:

AIR + MOISTURE
→ CAN LEAK INTO THE SYSTEM

Purge Unit

PURGE UNIT
→ removes noncondensables
→ minimizes refrigerant loss

Frequent purge operation can indicate air infiltration.

The purge unit is not the recovery machine for the entire chiller charge.

Leak Testing

Type III exam-preparation value:

10 psig
→ low-pressure leak-test maximum

This is an exam-preparation maximum, not a universal target pressure for every chiller.

Recovery Sequence

LIQUID FIRST
→ VAPOR SECOND
→ REQUIRED ENDPOINT
→ ISOLATE + CHECK REBOUND

No visible liquid does not mean recovery is complete.

Freeze Prevention

As refrigerant pressure falls:

SATURATION TEMPERATURE FALLS
→ WATER CAN FREEZE

During normal deep recovery:

CIRCULATE / MANAGE WATER AS REQUIRED

If a tube leak is suspected under the Type III exam procedure:

DRAIN EVAPORATOR WATER SIDE
+
DRAIN CONDENSER WATER SIDE
BEFORE RECOVERY

Refrigerant in Oil

Refrigerant can remain dissolved in oil and come out of solution as pressure falls.

Traditional Type III exam value:

130°F
→ oil-heating value before oil removal

Current oil-change pressure provision:

NO HIGHER THAN 5 psig

Charging

From a deep vacuum:

VAPOR FIRST
→ pressure rises
→ saturation temperature rises
→ freeze risk decreases
→ LIQUID LATER when approved

For blends, distinguish:

REMOVE BLEND FROM SOURCE AS LIQUID

from:

INTRODUCE VAPOR FIRST INTO
A DEEPLY EVACUATED LOW-PRESSURE CHILLER

Both can be correct in the same controlled charging procedure.

Type III Evacuation Requirement

25 mm Hg absolute

for the current normal low-pressure Table 1 refrigerant-removal endpoint.

25 mm Hg absolute
≠
25 in. Hg vacuum

Traditional Type III Exam Values

10 psig
→ leak-test maximum
10 psig
→ recovery-unit high-pressure cutout
15 psig
→ low-pressure recovery-vessel rupture-disc value
130°F
→ oil heating
5 psig
→ current oil-change opening provision
25 mm Hg absolute
→ normal low-pressure evacuation endpoint

Do not generalize the 15 psig recovery-vessel rupture-disc value into a universal chiller pressure-relief rating.

Type III Safety

REFRIGERANT MONITOR
→ refrigerant concentration
OXYGEN MONITOR
→ oxygen concentration
MACHINERY ROOM
≠
AUTOMATICALLY OSHA CONFINED SPACE

Before water-side service:

STOP / ISOLATE ENERGY
→ RELIEVE PRESSURE
→ VERIFY SAFE CONDITION

A stopped pump does not prove that water-side pressure is zero.


7. Highest-Priority Numbers

Memorize every number with its concept, condition, and unit.

Number / ValueWhat It Controls
2 lb or lessQualifying DIY MVAC small-can sales exception, with required unique fitting and self-sealing valve
5 lb or lessCharge limit within the complete Type I small-appliance definition
>15 lb full chargeOrdinary system-dependent recovery-equipment restriction unless permanent pump-out
≥50 lbCurrent Section 608 ODS leak-repair applicability threshold for qualifying appliances
200 lbType II evacuation-table charge boundary
45 / 170 / 355 psia @ 104°FPressure-category boundaries / very-high criterion
80% / 90%Type I recovery percentages under the applicable conditions
4 in. Hg vacuumType I alternative recovery endpoint; also appears in pre-1993 Table 1 rows
0 / 10 / 15 in. Hg vacuumMajor current post-1993 Type II Table 1 endpoints
25 mm Hg absoluteCurrent Type III Table 1 endpoint
30% / 20% / 10%Current Section 608 ODS leak-rate triggers
>4 in² + >15 minNumerical major-repair criterion
0 psigQualifying non-major / leaking-section ceiling when applicable
5 psigCurrent special oil-change pressure provision
10 psigType III leak-test exam maximum; separately, recovery-unit cutout exam value
15 psigType III recovery-vessel rupture-disc exam value
130°FTraditional Type III oil-heating exam value
3 yearsCommon retention period for several Section 608 records
Nov. 15, 1993Recovery/recycling-equipment date boundary

The Three Charge Numbers Most Often Confused

5 lb
→ TYPE I SMALL-APPLIANCE DEFINITION
15 lb
→ SYSTEM-DEPENDENT RECOVERY-EQUIPMENT RULE
50 lb
→ CURRENT SECTION 608 ODS LEAK-REPAIR APPLICABILITY
200 lb
→ TYPE II EVACUATION-TABLE BOUNDARY

8. Current Leak-Rule Separation

Section 608 ODS Framework

For qualifying appliances:

≥50 lb applicable ODS refrigerant

Current trigger rates:

IPR 30%
COMMERCIAL 20%
COMFORT 10%
OTHER 10%

Separate AIM Act HFC Framework

The project also identifies a separate current federal HFC leak-repair framework under 40 CFR Part 84.

Do not combine the two programs.

Key distinction:

SECTION 608 ODS RULE
≠
AIM ACT HFC RULE

When an exam question identifies the regulatory framework, use the conditions belonging to that framework.


9. Commonly Confused Terms

Do Not ConfuseCorrect Distinction
Recover / recycle / reclaimRemove / clean / reprocess and verify
psig / psiaAtmosphere reference / perfect-vacuum reference
in. Hg vacuum / mm Hg absoluteLarger-deeper / smaller-deeper
Core / UniversalCommon knowledge / Types I + II + III
Type II / Section 609Stationary medium/high/very-high pressure / MVAC service
High-pressure appliance / high sideWhole appliance category / circuit location
Low-pressure appliance / low sideWhole appliance category / circuit location
Functional compressor / compressor presentMust actually be able to assist recovery
Recovery cylinder / disposable cylinderRefillable / one-way
Major repair / any repairSpecific regulatory definition / general service work
Non-major / no evacuation ruleNon-major work still requires checking the applicable provision
Current leak rates / historical rates30/20/10 / legacy 35/15 framework
EPA requirement / provider policyFederal rule / test-administration procedure
Recovery endpoint / dehydration targetRefrigerant-removal rule / technical moisture-removal target

10. Highest-Priority Universal Exam Traps

Trap 1 - Correct Number, Wrong Rule

15 lb
50 lb
200 lb

are not interchangeable.

Always identify what the number controls.

Trap 2 - Correct Rule, Wrong Appliance

A Type I recovery percentage is not a Type II evacuation requirement.

A Type III vacuum value is not a Type II value.

Trap 3 - Charge Alone Determines Type I

≤5 lb
≠
automatically small appliance

All four small-appliance conditions are required.

Trap 4 - November 15, 1993 Means Appliance Date

Wrong.

For the recovery requirements emphasized in this course:

NOV. 15, 1993
→ RECOVERY / RECYCLING EQUIPMENT DATE

Trap 5 - Historical Leak Rates Used as Current

35% / 15%
→ historical

Current Section 608 ODS trigger table:

30% / 20% / 10%

Trap 6 - High Side Means Type II

Wrong.

HIGH SIDE
→ refrigeration-cycle location
TYPE II
→ appliance certification category

Trap 7 - Low Side Means Type III

Wrong.

A Type II system also has a low side.

Trap 8 - Failed Compressor Removes Recovery Requirement

Wrong.

The recovery method changes; the recovery requirement remains.

Trap 9 - No Visible Liquid Means Recovery Complete

Wrong.

Vapor, dissolved refrigerant, or trapped refrigerant can remain.

Trap 10 - Deep-Vacuum Type III Charging Starts With Liquid

Wrong.

VAPOR FIRST
→ LIQUID LATER

Trap 11 - 25 mm Hg Absolute Equals 25 in. Hg Vacuum

Wrong.

The units and reference points are different.

Trap 12 - Purge Unit Is a Recovery Machine

Wrong.

The purge unit removes noncondensables while minimizing refrigerant loss.

Trap 13 - Provider Policy Is EPA Law

Wrong.

Time limits, attempt counts, waiting periods, software, and credential-delivery procedures are provider-specific.

Trap 14 - Universal Includes Section 609

Wrong.

Universal is:

TYPE I + TYPE II + TYPE III

Paid ordinary MVAC service still requires the applicable Section 609 credential.

Trap 15 - Good Practice Automatically Equals the Federal Minimum

A manufacturer or technical service procedure may require a deeper vacuum or additional steps beyond the Section 608 refrigerant-removal endpoint.

Know what the question is asking.


11. Five-Step Question Method

For every question:

1. WHAT APPLIANCE / SECTION IS THIS?
2. WHAT CONDITION CONTROLS?
3. WHAT RULE OR PHYSICAL PRINCIPLE APPLIES?
4. WHAT UNIT / DATE / THRESHOLD IS USED?
5. WHICH CHOICE ANSWERS THE EXACT QUESTION?

Watch especially for:

NOT
EXCEPT
MINIMUM
MAXIMUM
FIRST
LAST
CURRENT
HISTORICAL
REQUIRED
PROHIBITED

A distractor is often a true statement that belongs to a different appliance, condition, date, or regulatory program.


12. Final Exam-Day Reading Checklist

Immediately before the official examination, read this section once.

Knowledge

  • I can classify Type I, Type II, and Type III equipment before choosing a procedure.
  • I know the complete small-appliance definition.
  • I know the 5 / 15 / 50 / 200 lb distinctions.
  • I know the Type I 80% / 90% / 4 in. Hg vacuum rules.
  • I know the Type II current evacuation table.
  • I know the Type III 25 mm Hg absolute requirement.
  • I know current Section 608 ODS leak rates are 30% / 20% / 10%.
  • I can separate current rules from historical values.
  • I can separate EPA regulations from provider policies.
  • I have no unresolved high-priority safety or regulatory errors.

Test Setup

  • I have confirmed the certifying organization is currently EPA approved.
  • I have read the provider’s current candidate instructions.
  • I know the current time limit and scoring / section-credit method.
  • I know what materials, calculator, P-T chart, or scratch materials are permitted.
  • Identification is ready.
  • Account login works.
  • Camera, microphone, device, and internet are ready if remotely proctored.
  • The testing area is quiet and compliant.
  • Unauthorized notes and devices are removed.

During the Exam

  • Read the entire stem before looking for a familiar number.
  • Identify the appliance or certification section.
  • Mark NOT, EXCEPT, MINIMUM, MAXIMUM, FIRST, and similar controlling words mentally.
  • Check units.
  • Eliminate choices that belong to another Type or another condition.
  • Do not spend excessive time on one question.
  • Return to uncertain questions if time remains.
  • Change an answer only for a specific technical or reading reason.
  • Do not use outside help or unauthorized materials.

Final Reminder

CLASSIFY FIRST
→ FIND THE CONTROLLING CONDITION
→ APPLY THE CORRECT RULE
→ CHECK THE UNIT
→ ANSWER ONLY WHAT WAS ASKED

13. Project Readiness Standard

Before the official Universal attempt:

CORE ≥22/25
TYPE I ≥22/25
TYPE II ≥22/25
TYPE III ≥22/25

on:

TWO SEPARATE
CLOSED-BOOK
CUMULATIVE ATTEMPTS

and:

ZERO UNRESOLVED P1 ERRORS

This is the project’s preparation standard, not the federal passing-score rule.

If any section has not met the target, return to:

  • 10.10 - Error Analysis and Remediation.md
  • 10.13 - Optional Remediation Examination.md
  • 10.14 - Official Examination Readiness Checklist.md

14. Final Universal Memory Map

CORE
→ environment + regulation + refrigerants
→ recovery + cylinders + evacuation + safety
TYPE I
→ small appliance
→ all four definition conditions
→ 80 / 90 / 4
→ operating vs failed compressor
TYPE II
→ medium + high + very high
→ 45 / 170 / 355
→ liquid first where practical
→ 15 / 50 / 200 are different rules
→ 0 / 4 / 10 / 15 evacuation values
TYPE III
→ low pressure
→ air + moisture can leak IN
→ purge
→ liquid first / vapor second recovery
→ freeze prevention
→ vapor-first charging
→ 25 mm Hg absolute
UNIVERSAL
→ CORE + TYPE I + TYPE II + TYPE III
FINAL EXAM HABIT
→ CLASSIFY
→ CONDITION
→ RULE
→ UNIT
→ ANSWER

References

Current Regulatory and EPA Sources

  1. U.S. Environmental Protection Agency, Section 608 Technician Certification Requirements, project verification August 14, 2026.

  2. U.S. Environmental Protection Agency, Section 608 Test Topics, project verification August 14, 2026.

  3. U.S. Environmental Protection Agency, Required Level of Evacuation of Appliances, project verification August 14, 2026.

  4. U.S. Environmental Protection Agency, Stationary Refrigeration Service Practice Requirements, project verification August 14, 2026.

  5. U.S. Environmental Protection Agency, Stationary Refrigeration Leak Repair Requirements, project verification August 14, 2026.

  6. Electronic Code of Federal Regulations, 40 CFR Part 82, Subpart F - Recycling and Emissions Reduction, project verification August 14, 2026.

Module 10 Review Files

  1. 10.1 - Universal Certification Comparison Tables

  2. 10.2 - High-Priority Numbers and Thresholds

  3. 10.3 - Commonly Confused Terms

  4. 10.4 - Core Memorization Sheet

  5. 10.5 - Type I Memorization Sheet

  6. 10.6 - Type II Memorization Sheet

  7. 10.7 - Type III Memorization Sheet

  8. 10.10 - Error Analysis and Remediation

  9. 10.15 - Official Examination Readiness Checklist